
Add to Cart
Product Discription
YY (q) w Caldeira, also known as organic boiler for heating, uses oil and gas As fuel, hot oil As a medium of circulation, medium liquid, transfers thermal energy to the USO of thermal equipment, returns to the R heater and then warmed by the Heat obtained May meet the requirements of the boiler. The acquisition of the low temperature is characterised by the acquisition of the low temperature. The liquid heating temperature can reach 320 and the steam temperature can reach 400. The internal, medium and external (or internal and external) circulars with a narrow arrangement. The internal coil absorbs most of the heat from the radiation heating surface, and the high temperature flow gas enters the convetive heating surface. Nd. The combustion gas from the Caldeira is absorbed by the heat exchanger at the end of the Caldeira and discharged into the atmosphere through the chimney.
Product Features
1. High security:
It is controlled by the computer and has thermal colour protection, temperature protection and voltage protection that is safe and reliable.
2. Long service life and durability:
Excellent professional design, advanced manufacturing technology, strict quality control and control are the quality assurance of each boiler. The normal life of the boiler is more than 20 -years.
3. Environmental protection and low noise pollution:
The exhaust emission of the boiler is low, with waste heat recovery, high efficiency vacuum cleaner, low noise emission, so that the exhaust gas emission complies with national environmental protection requirements.
4. Production standards:
The boiler components are manufactured according to national and international standards (ISO). All processes strictly follow advanced production technology to ensure product quality.
5. Good service:
Technical advice, technical services, installation instructions, regular and irregular tracking services for users, at any time to provide quality and perfect services to ensure that our customers buy safely and use happily.
Technical Parameters
Main Technical parameters of YY(Q)W Series Horizontal Oil & Gas Fired Thermal Oil Boiler | ||||||||
Item | Unit | YY(Q)W -1400Y(Q) | YY(Q)W -2100Y(Q) | YY(Q)W -3000Y(Q) | YY(Q)W -4200Y(Q) | YY(Q)W -6000Y(Q) | YY(Q)W -7000Y(Q) | |
Thermal Power | KW | 1400 | 2100 | 3000 | 4200 | 6000 | 7000 | |
Heat Supply | 104Kcal/h | 120 | 180 | 250 | 360 | 500 | 600 | |
Working Pressure | MPa | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | |
Rated oil output temperature | ℃ | 300 | 300 | 300 | 300 | 300 | 320 | |
Rated oil return temperature | ℃ | 280 | 280 | 280 | 280 | 280 | 300 | |
Thermal Efficiency | / | ≥92% | ||||||
Fuel | / | Natural gas, liquefied gas, city gas, light oil | ||||||
Fuel Consumption | Natural gas | NM3/h | 163 | 243 | 349 | 489 | 692 | 809 |
Liquefied gas | Kg/h | 127.7 | 189.9 | 269 | 376.8 | 535.7 | 624.8 | |
City gas | NM3/h | 347.9 | 518.7 | 738.3 | 1036 | 1465.4 | 1706 | |
Light oil | Kg/h | 139.3 | 203 | 287.3 | 415.2 | 571 | 665 | |
Gas Feed pressure | Natural Gas | mbar | 50-100 | 50-100 | 50-100 | 50-100 | 100-200 | 100-200 |
City Gas | mbar | 70-200 | 70-200 | 70-200 | 70-200 | 100-200 | 100-200 | |
Rated circulating oil quantity | M3/h | 82.95 | 125.5 | 177.7 | 248.8 | 355 | 413 | |
Mainframe Oil Volume | M3 | 1.19 | 1.6 | 2.2 | 3.92 | 4.3 | 5.9 |
Note: the fuel consumption in the table is based on light oil low calorific value 42915KJ/Kg (10260Kcal/Kg), natural gas low calorific value 35588KJ/NM3 (8500Kcal/NM3) and liquefied gas low calorific value 45998KJ/Kg (11000Kcal/Kg). Calculation of low calorific value (16750KJ/NM3 (4000Kcal/NM3) of urban gas.
Shape and Interface Dimensions of YY(Q)W Series Horizontal Oil & Gas Fired Thermal Oil Boiler | ||||||
Item | Unit | YY(Q)W -3000Y(Q) | YY(Q)W -4200Y(Q) | YY(Q)W -6000Y(Q) | YY(Q)W -7000Y(Q) | |
Transport Dimension (L*W*H) | / | mm | 5808*2505*2820 | 7082*2970*3140 | 8100*3190*3430 | 8910*3370*3620 |
Mainframe transport weight | / | t | 11 | 18 | 26 | 30 |
Outlet Diameter | DN | mm | 150 | 200 | 200 | 250 |
Return Pipe Diameter | DN | mm | 150 | 200 | 200 | 250 |
Drain Valve Pipe Diameter | DN | mm | / | / | / | / |
Discharge Pipe Diameter | DN | mm | 40 | 40 | 40 | 50 |
Chimney Diameter | φ | mm | 500 | 600 | 700 | 800 |
Remarks: We will reserve rights to change the above mentioned data due to continuous policy transformation and product improvement.